Submittal Sheet
Table Of Contents
7800 SERIES S7800A2142 KEYBOARD DISPLAY MODULE
32-00110—05 40
a
European approved controls
b
Pre-ignition Interlock terminal 17 or 20 is model dependent.
c
Valve Proving device or RM7897
d
Display values are as follows:
• n represents a numbered value
• T represents a terminal number
• x represents the suffix letter of the Relay module
e
Burner control terminal name is displayed.
f
Assigned annunciator terminal name is displayed.
Editing of this feature is accessed by selecting “Selected status” from the Display Setup menu (see Fig. 58). The current
parameter setting is displayed when the page is initially entered.
Fig. 58. Selected status message setup
The up and down arrow buttons are used to scroll through the message choices on the edit line. The right and left arrow
buttons are used to tab to the save commands, “Yes” and “No”. When the input focus is on the save commands the up and
down arrow buttons scroll between “Yes” and “No”. When the message is set to the value desired the “Yes” command is
selected and the OK button is pressed to commit the change. If the user decides not to save the displayed message
choice, the “No” command is selected and the OK button is pressed. In both save command cases control returns back to
the Display setup menu.
T12 Oil select
f
Annunciator Oil selection. ON or OFF Indicates if interlock is on or off.
T13 High oil pressure
f
Annunciator High oil
pressure.
ON or OFF Indicates if interlock is on or off.
T14 Low oil pressure
f
Annunciator Low oil
pressure.
ON or OFF Indicates if interlock is on or off.
T15 High oil temp
f
Annunciator High oil
temperature.
ON or OFF Indicates if interlock is on or off.
T16 Low oil temp
f
Annunciator Low oil
temperature.
ON or OFF Indicates if interlock is on or off.
T17 Gas select
f
Annunciator Gas selection. ON or OFF Indicates if interlock is on or off.
T18 High gas pressure
f
Annunciator High gas
pressure.
ON or OFF Indicates if interlock is on or off.
T19 Low gas pressure
f
Annunciator Low gas
pressure.
ON or OFF Indicates if interlock is on or off.
T19 Atomizing
f
Annunciator Atomizing
switch.
ON or OFF Indicates if interlock is on or off.
T20 Airflow
f
Annunciator Airflow switch. ON or OFF Indicates if interlock is on or off.
T21 Aux ILK 4
f
Annunciator Auxiliary ILK
#4.
ON or OFF Indicates if interlock is on or off.
T22 Aux ILK 5
f
Annunciator Auxiliary ILK
#5.
ON or OFF Indicates if interlock is on or off.
Annun fault code Annunciator fault code.
Annun SW revision Annunciator software
revision.
Table 6. Selectable Messages. (Continued)
Selectable
Message/Display Description
Possible States/Range
(Terminals) Comments