Submittal Sheet

RP SERIES THREE-WAY SOLENOID AIR VALVE
Honeywell Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
® U.S. Registered Trademark
©2020 Honeywell International Inc.
31-00391—01 M.S. 07-20
Printed in United States
This air valve may be mounted in any position. It can be
supported by the piping, when used, or conduit to which it
is attached. When tubing is used, the bracket supplied on
the valve may be used for adequate support. Tubing
connections are made to the barbed connectors.
Check the voltage shown on the valve data plate against
the voltage of the power source to see that the right unit is
being installed.
WIRING
CAUTION
Risk of Electric Shock.
Disconnect the power supply before making
electrical connections to avoid electric shock.
MISE EN GARDE
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
All wiring must conform to the National Electrical Code
and local regulations.
Make wiring connections to the 18 in. wire leads from the
coil. The wire is brought through a 7/8 in. diameter
conduit opening in the end of the case. All splices should
be made using approved solderless connectors or by
soldering and then taping the connections.
Fig. 2. RB Three-Way Solenoid Air Valve. Optional
manual opener key is shown in the proper position for
insertion.
SPECIFICATIONS
Air Connections: 1/4 in. Barb Connections in Common
Port and Normally Closed Port;
Normally Open Port is 1/8 in. NPT (Internal)
AMBIENT TEMPERATURES
Alternating Current Models: Minimum 32ºF (0ºC);
Maximum 140ºF (60ºC)
Direct Current Models: Minimum 32ºF (0ºC);
Maximum 104ºF (40ºC)
Conduit Opening: 7/8 in. Diameter
FINISH
Valve Body: Dull Gray (Iridate)
Cover and Case: Gray Baked Enamel
MATERIAL
Valve Body: Die Cast Aluminum
Cover and Case: Cold, Rolled Steel
Maximum Pressure Rating: 30 psig (210 kPa)
Operating Pressure (All Three Ports): 0 to 20 psig
(0 to 138 kPa)
POWER CONSUMPTION
Alternating Current Models: 6 Watts
24 VDC Models: 9 Watts
Pressure and Flow Ratings: With a 15 psig (103 kPa)
Inlet and 0 psig (0 kPa) Outlet. The valve will pass
1.5 cfm (2592 scim [0.71l/s]) of air from the Common
to the Normally Closed connection (when energized) or
from the Common to the Normally Open connection
(when de-energized).
Wiring Connections: 18 in. Wire Leads
Agency Listing: UL Guide No. YIOZ, UL file MH3536.
Table 1. Models.
Product
Number Description
RP419B1071 110/120V, 50/60Hz, Lead wire connection.
RP419A1107 110/120V, 50/60Hz, Junction box and Lead wire
connections.
RP419A1057 120V, 60Hz, Junction box and Lead wire connections.
RP419A1081 208V, 60Hz, Junction box and Lead wire connections.
RP419A1065 480V/60Hz or 440V/50Hz, Junction box and Lead
wire connections.
RP819B1002 24V, 60Hz, Lead wire connection.
RP819A1004 24V, 60Hz, Junction box and Lead wire connections.
RP819B1010 24V, 50Hz, Lead wire connection.