RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
66-1161—04 2
WARNING
Explosion Hazard
Can cause severe injury, death or property damage.
Be sure to select adequate testing times when the
Valve Proving feature is enabled. A shorter time can
result in inadequate leak testing of the valves.
This document provides installation and static checkout
instructions. Other applicable publications are:
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency:
RM7898: 120 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form 65-0312 for Certificate Agreement.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Canadian Standards Association Certified: File Number
0X4A5.AF
Factory Mutual Approved: Report No. Pending.
SwissRe (formerly IRI) Acceptable.
Federal Communications Commission: Part 15, Class B,
Emissions.
INSTALLATION
When Installing this Product…
1.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property damage.
Follow applicable safety requirements when installing
a control on a burner to prevent death or severe injury.
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or equipment
damage.
Disconnect power supply before beginning installation.
More than one disconnect may be required.
Publication
No. Product
65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0288 S7800A1142 Keyboard Display Module
Product Data
65-0091
S7810A Data ControlBus™ Module Product Data
65-0095
S7820 Remote Reset Module Product Data
65-0097
221729C Dust Cover Installation Instructions
65-0101 S7830 Expanded Annunciator Product Data
65-0109 R7824, R7847, R7848, R7849, R7851,
R7861, R7886 Flame Amplifiers for the
7800 SERIES Product Data
65-0131 221818A Extension Cable Assembly
Product Data
65-0229 7800 SERIES Relay Modules Checkout and
Troubleshooting Product Data.
65-0249 S7810M ModBus Module