Install Instructions
41 65-0100—2
12
Q7800
13
14
15
16
18
17
19
20
21
22
G
L2
9
8
7
6
5
4
3
10
F
G
2 (L2) + 15
9
8
4
7
M2521B
A
5,6
MAIN VALVE
10
IGNITION
TRANSFORMER
FOR DIRECT SPARK IGNITION
(OIL OR GAS)
8
9
L2
GENERAL FOOTNOTES, SEE PAGE 5.
A
B
1234
5
7815
18
16
B
F
E
C
7800 SERIES CONVERSION WIRING DIAGRAM
FROM________________________________ TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)
1 (L1) + 3
R4181A1000, A1026
RM7840E1016 OR RM7800E1010
RM7840L1018 OR RM7800L1012
C
E
F
G
G
D
D
R4181A, TERMINAL 6, PROVIDES 30
SECOND MFEP. REPLACEMENT
RM7840/RM7800 PROVIDES 15
SECONDS ONLY.
REMOVE AND DISCARD ANY JUMPERS
BETWEEM Q477 OR Q514 SUBBASE
TERMINALS F TO 14 OR F TO 16.
RM7840L/RM7800L ONLY – LOCATE LOW
FIRE SWITCH CONNECTED TO Q477 OR
Q514 SUBBASE TERMINAL 1(L1) AND
CONNECT TO Q7800 SUBBASE TERMINAL 5.
IF LOWFIRE SWITCH IS NOT USED,
CONNECT A JUMPER FROM TERMINAL 18
TO 5. NOTE: THIS JUMPER WILL EXTEND
PREPURGE TIME BY 30 SECONDS.
RM7840L/RM7800L – CONNECT JUMPER
BETWEEN Q7800 SUBBASE TERMINALS 5
AND 19. NOTE: THIS WILL EXTEND
PREPURGE TIME BY 30 SECONDS.
RM7840E/RM7800E – CONNECT JUMPER
BETWEEN Q7800 SUBBASE TERMINALS 4
AND 19. NOTE: THIS JUMPER WILL
EXTEND PREPURGE TIME BY 30
SECONDS.
NOTE: R4181 TERMINAL 16 MAY HAVE
BEEN USED FOR THE FLAME DETECTOR.
IF R4181 TERMINAL 16 IS NOT CONNECTED
TO R4181 TERMINAL F, CONNECT R4181
TERMINAL 16 TO Q7800 TERMINAL 22.
LOCATE THIS JUNCTION
AND CONNECT IT TO
Q7800 SUBBASE
TERMINAL 6
LOCATE THE START INTERLOCKS AT THIS POINT AND
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.
LIMITS
CONTROLLER
START
INTERLOCKS
AIRFLOW
SWITCH
L1 3
4
18
16
11
10
12
13
17
F
For Insurance Requirements