Install Instructions
65-0100—2 34
12
Q7800
13
14
15
16
18
17
19
20
21
22
G
L2
9
8
7
6
5
4
3
10
F
G
L2
9
8
4
7
M2511B
A
6
F1
MAIN VALVE
10
IGNITION
TRANSFORMER
FOR DIRECT SPARK IGNITION
(OIL OR GAS)
8
9
L2
GENERAL FOOTNOTES, SEE PAGE 5.
A
B
E
1234
5 7815
18
B
D
C
B
5
7800 SERIES CONVERSION WIRING DIAGRAM
FROM________________________________ TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)
L1&3
R4126A1073, A1164
RM7840E1016 OR RM7800E1010
RM7840L1018 0R RM7800L1012
C
E
D
LOCATE LOW FIRE SWITCH WIRE ON Q535
OR Q536 SUBBASE TERMINAL 15 AND
CONNECT TO Q7800 SUBBASE TERMINAL 5.
IF LOWFIRE SWITCH IS NOT USED, INSTALL
A JUMPER. NOTE: JUMPER WILL ADD 30
SECONDS TO PREPURGE TIMING.
RN7840L/RM7800L–LOCATE Q535 OR Q536
SUBBASE L1 SIDE OF HIGH FIRE SWITCH
AND CONNECT TO Q7800 SUBBASE
TERMINAL 5. IF HIGH FIRE SWITCH IS NOT
USED, INSTALL A JUMPER. NOTE: JUMPER
WILL ADD 30 SECONDS TO PREPURGE
TIMING.
Q535 OR Q536 SUBBASE HAD U1 AND U2
TERMINALS THAT WERE USED FOR
C7020 AND C7012E,F FLAME DETECTORS.
A. TO MODERNIZE C7020 APPLICATIONS,
CHOOSE A NEW DECTOR AND
REWIRE PER RM7840/RM7800
SPECIFICATIONS.
B. TO MODERNIZE A C7012E,F
APPLICATION, USE THE EXISTING
SENSOR AND REWIRE PER
RM7840/RM7800 SPECIFICATIONS.
LOCATE THIS JUNCTION
AND CONNECT IT TO
Q7800 SUBBASE
TERMINAL 6
LOCATE THE START INTERLOCKS AT THIS POINT AND
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.
LIMITS
CONTROLLER
START
INTERLOCKS
AIRFLOW
SWITCH
L1 3
4
16
12
13
14
11
15