Specifications

Relays
164 customer.honeywell.com 70-6910
R8330 Electric Furnace Sequencer
One control switches a fan and up to three elements on and off in
sequence.
Isolated fan switch has positive interlock to assure fan is on when
the element is on, and fan is off when the element is off.
Replaces any of the ten models in our line and many competitive
devices.
Combination rating on the first element switch allows replacing
devices having fan and first element controlled by the same switch
without rewiring the furnace.
Auxiliary switch controls a second R8330 in application with more
than three elements.
Cycles ON within two minutes, OFF within four minutes.
Ten-second minimum delay between stages (makes sequence and
break sequence.)
Timings meet EEI-NEMA and ARI 280 Standards.
Dimensions, Approximate: 3 1/16 in. high x 4 13/16 in. wide x 2 11/32
in. deep (78 mm high x 122 mm wide x 60 mm deep.)
Electrical Connections (main): terminals
Temperature Rating: -20 F to +150 F (-29 C to +66 C)
Approvals:
Canadian Standards Association: Certified
Underwriters Laboratories, Inc. UL Listed
R841 Electric Heating Relay
Use with two-wire, 24 Vac thermostat to control electric heating
equipment such as baseboard, ceiling cable and duct heaters.
Operate with each cycle of the thermostat (4 to 6 cycles per hour).
Each relay switches up to a 5,000 W load.
Contacts make and break in about 75 seconds.
Mount in any position.
Includes 1/2 in. (13 mm) male conduit bushing.
Dimensions, Approximate: 3 7/8 in. high x 2 13/16 in. wide x 1 1/2 in.
deep (98 mm high x 71 mm wide x 38 mm deep)
Temperature Rating: -20 F to +150 F (-29 C to +66 C)
Approvals:
Canadian Standards Association: Certified
Underwriters Laboratories, Inc. UL Listed
Electrical Ratings, Contacts
(Full Load) (Locked Rotor)
3/4 hp; 6.9 A @ 120 Vac, 208 Vac, 240 Vac;
1/3 hp; 7.2 A @ 120 vac; 4.9 A @ 277 Vac
3/4 hp; 41.4 A @ 120 Vac, 208 Vac, 240 Vac
1/3 hp; 43.2 a @ 120 Vac; 29.4 A @ 277 Vac
Product Number Coil Ratings Voltage Frequency
* R8330D1039 24 Vac 60 Hz
* TRADELINE models • SUPER TRADELINE models
Electrical Ratings, Contacts
(Full Load) (Locked Rotor) (Resistive)
14 A @ 120 Vac;
7.0 A @ 208 Vac, 240 Vac, 277 Vac
84 A @ 120 Vac;
42 A @ 208 Vac, 240 Vac, 277 Vac
22 A @ 120 Vac, 208 Vac, 240 Vac;
19 a @ 277 Vac
Product Number
Coil Ratings
Voltage Frequency Switching
Electrical Connections
(main) Includes
R841C1029 240 V 50 Hz; 60 Hz SPST Terminals Enclosure w/conduit bushing.
R841C1151 600 Vac 50 Hz; 60 Hz SPST Leadwires Enclosure w/ conduit bushing and an integral
transformer.
* R841C1169 208 V; 240 Vac 50 Hz; 60 Hz SPST Leadwires Enclosure w/ conduit bushing and an integral
transformer.
* R841C1227 24 V 50 Hz; 60 Hz SPST Leadwires
* R841D1036 24 V 50 Hz; 60 Hz SPST Leadwires Enclosure w/conduit bushing.
* R841E1068 24 V 50 Hz; 60 Hz SPST Leadwires Enclosure w/conduit bushing and integral
transformer; dual load.
* TRADELINE models • SUPER TRADELINE models