Specifications
Relays
164 customer.honeywell.com 70-6910
R8330 Electric Furnace Sequencer
One control switches a fan and up to three elements on and off in
sequence.
• Isolated fan switch has positive interlock to assure fan is on when
the element is on, and fan is off when the element is off.
• Replaces any of the ten models in our line and many competitive
devices.
• Combination rating on the first element switch allows replacing
devices having fan and first element controlled by the same switch
without rewiring the furnace.
• Auxiliary switch controls a second R8330 in application with more
than three elements.
• Cycles ON within two minutes, OFF within four minutes.
• Ten-second minimum delay between stages (makes sequence and
break sequence.)
• Timings meet EEI-NEMA and ARI 280 Standards.
Dimensions, Approximate: 3 1/16 in. high x 4 13/16 in. wide x 2 11/32
in. deep (78 mm high x 122 mm wide x 60 mm deep.)
Electrical Connections (main): terminals
Temperature Rating: -20 F to +150 F (-29 C to +66 C)
Approvals:
Canadian Standards Association: Certified
Underwriters Laboratories, Inc. UL Listed
R841 Electric Heating Relay
Use with two-wire, 24 Vac thermostat to control electric heating
equipment such as baseboard, ceiling cable and duct heaters.
• Operate with each cycle of the thermostat (4 to 6 cycles per hour).
• Each relay switches up to a 5,000 W load.
• Contacts make and break in about 75 seconds.
• Mount in any position.
• Includes 1/2 in. (13 mm) male conduit bushing.
Dimensions, Approximate: 3 7/8 in. high x 2 13/16 in. wide x 1 1/2 in.
deep (98 mm high x 71 mm wide x 38 mm deep)
Temperature Rating: -20 F to +150 F (-29 C to +66 C)
Approvals:
Canadian Standards Association: Certified
Underwriters Laboratories, Inc. UL Listed
Electrical Ratings, Contacts
(Full Load) (Locked Rotor)
3/4 hp; 6.9 A @ 120 Vac, 208 Vac, 240 Vac;
1/3 hp; 7.2 A @ 120 vac; 4.9 A @ 277 Vac
3/4 hp; 41.4 A @ 120 Vac, 208 Vac, 240 Vac
1/3 hp; 43.2 a @ 120 Vac; 29.4 A @ 277 Vac
Product Number Coil Ratings Voltage Frequency
* R8330D1039 24 Vac 60 Hz
* TRADELINE models • SUPER TRADELINE models
Electrical Ratings, Contacts
(Full Load) (Locked Rotor) (Resistive)
14 A @ 120 Vac;
7.0 A @ 208 Vac, 240 Vac, 277 Vac
84 A @ 120 Vac;
42 A @ 208 Vac, 240 Vac, 277 Vac
22 A @ 120 Vac, 208 Vac, 240 Vac;
19 a @ 277 Vac
Product Number
Coil Ratings
Voltage Frequency Switching
Electrical Connections
(main) Includes
R841C1029 240 V 50 Hz; 60 Hz SPST Terminals Enclosure w/conduit bushing.
R841C1151 600 Vac 50 Hz; 60 Hz SPST Leadwires Enclosure w/ conduit bushing and an integral
transformer.
* R841C1169 208 V; 240 Vac 50 Hz; 60 Hz SPST Leadwires Enclosure w/ conduit bushing and an integral
transformer.
* R841C1227 24 V 50 Hz; 60 Hz SPST Leadwires —
* R841D1036 24 V 50 Hz; 60 Hz SPST Leadwires Enclosure w/conduit bushing.
* R841E1068 24 V 50 Hz; 60 Hz SPST Leadwires Enclosure w/conduit bushing and integral
transformer; dual load.
* TRADELINE models • SUPER TRADELINE models