How to Guide
IMPORTANT
THE SPEClFlCATlONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING
TOLERANCES. THEREFORE, UNITS MAY NOT MATCH THE LISTED SPECIFICATIONS EXACTLY. ALSO,
PRODUCTS ARE TESTED AND CALIBRATED UNDER CLOSELY CONTROLLED CONDITIONS, AND SOME
MINOR DIFFERENCES IN PERFORMANCE CAN BE EXPECTED IF THOSE CONDITIONS ARE CHANGED.
TRADELINE MODELS
TRADELINE models are selected and packaged for
ease of handling, ease of stocking, and maximum
replacement value. TRADELINE model specifica-
tions are the same as those of standard models,
except as noted.
TRADELINE MODELS:
R8184M Protectorelay Oil Primary Control
TRADELINE FEATURES:
MANUAL TRIP SAFETY SWITCH LEVER: Tradeline
models include a lever to manually trip the safety
switch.
LOCKOUT INDICATOR LIGHT: Tradeline models in-
clude a light emitting diode (LED) on the terminal
strip that lights to indicate when the oil primary
control has locked out on safety.
STANDARD MODELS
MODELS:
R8184M Protectorelay Oil Primary Control
ELECTRICAL RATINGS:
Transformer: 40 VA
Primary Voltage: 12OV, 60 Hz.
Secondary Voltage: 26.5V, 60 Hz.
Load Relay Contacts:
Full Load: 7.4A.
Locked Rotor: 44.4A.
Ignition Rating: 360 VA (in addition to the load relay
rating)
Power Consumption:
Start: 9.OA
Running: 6.5A
SAFETY SWITCH TIMING: 45 seconds.
IGNITION SEQUENCE: All models provide intermittent
ignition. Ignition is on whenever the burner is on.
THERMOSTAT HEAT ANTICIPATOR SETTING: Models
available for 0.2A thermostat heat anticipator setting.
AMBIENT TEMPERATURE RANGE: -40” F to 130” F
[-40” c to 54” C].
MOUNTING: Mounts on a standard 4 x 4 inch junction box.
DIMENSIONS: Refer to Figs. 1 and 2.
FLAME DETECTOR (order separately): C554A Cadmium
Sulfide Cell.
APPROVALS:
UNDERWRITERS LABORATORIES INCOR-
PORATED COMPONENT RECOGNIZED: File
Number MP268, Guide Number MCCZ2.
:. .:.. . . . . .::.
i~:~:::-:aw’BERi’~~:~iNF~~~~~~~~~~:I_rI~~~~~~~
. . ...:
FOR ORDERING INFORMATION WHEN PURCHASING REPLACEMENT AND MODERNIZATION PRODUCTS
FROM YOUR TRADELINE WHOLESALER OR YOUR DISTRIBUTOR, REFER TO THE TRADELINE CATALOG
OR PRICE SHEETS FOR COMPLETE ORDERING NUMBER, OR SPECIFY:
1. Order number. Tradellne If desired.
2. Heat anticipator setting.
IF YOU HAVE ADDlTlONAL QUESTIONS, NEED FURTHER INFORMATION, OR WANTTO COMMENT ON OUR
PRODUCTS OR SERVICES, PLEASE WRITE OR PHONE:
1. YOUR LOCAL HONEYWELL RESIDENTIAL AND BUILDING CONTROLS SALES OFFICE (CHECK
WHITE PAGES OF PHONE DIRECTORY).
2. RESlDENTlAL AND BUILDING CONTROLS CUSTOMER SATlSFACTlON
HONEYWELL INC., 1885 DOUGLAS DRIVE NORTH
MINNEAPOLIS, MINNESOTA 55422
(612) 542-7500
IN CANADA: HONEYWELL CONTROLS LIMITED
740 ELLESMERE ROAD
SCARBOROUGH, ONTARIO MlP 2V9
INTERNATlONAL SALES AND SERVICE OFFICES IN ALL PRINCIPAL ClTlES OF THE WORLD.
2