Service Manual

TROUBLESHOOTING GUIDE
95C-10906-02
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
95C-10906—02 M.S. Rev. 07-11
Printed in U.S.A.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
Troubleshooting Guide for
ML Valve Actuator
Emergency Field Calibration for ML7984A
This is a rough calibration only. DO NOT CHANGE THE FACTORY CALIBRATIONS UNLESS ABSOLUTELY NECESSARY!
1. Set the controller signal to its mid value (i.e. 6 Vdc, 12 mA or 67.5 R) with a digital meter connected.
2. Measure the distance between the bottom of yoke (top of valve bonnet) to the bottom/tip of the brass output drive shaft with
a caliper, measuring tape or ruler.
3. Insert a 5 mm wide flat bladed screwdriver into the T-shaped slot on the BLACK feedback pot. (the one that attached to the
brass drive shaft).
4. Turn the pot. so that the actuator will respond with travel either upward or downward until the reading on the caliper shows:
68.8 mm (for ML7984A3001) or 71.8 mm (for ML7984A3019).
5. Tag the actuator with reference to this modification, i.e. The device has been modified to ML7984A3019.
SYMPTOM POSSIBLE CAUSES ACTIONS
Valve leaks or will not
close off fully
System pressure too high
Actuator not properly installed
Incorrect DIP switch settings
Check Valve Close-off rating, and ML & Valve combinations:
Ensure valve stem is fully threaded into brass drive shaft &
locked in place with the set screw
Check against Product Instruction Sheet
Noisy motor Bearing failed due to overheat
Brushes worn out
Check for excessive temperature and replace complete
actuator
High Temperature Kit is available; 43196000-001
Check for excessive cycling
Motor overheats/smoke/
component burnt-out
Current sensing circuit failed or
electronic components failed
Replace actuator. Make sure:
Correct actuator used
Properly installed
Do not adjust any calibration pot.
Proper voltage supply
Applied according to ML specifications
ML will not respond Incorrect DIP switch settings
No or low power supply
No control signal present
Incorrect wiring connections
Incorrect signal polarity
Internal time delay
Check against Product Instruction Sheet
Check voltage on T5 & T6 terminals
Check controller
Check against Product Instruction Sheet
Check against Product Instruction Sheet
Allow >1 second for the ML to respond
Vdc/mA signal drops when
connected to ML
Signal degradation due to
incompatible load impedance
Check Controller Output and ML Input Impedance
specifications
ML6984 will not close or
lock-up when used with
T87
T87 Cooling Anticipator caused
current shunting to the ML
Use Series 2- ML6984 (Date Code 0049) or cut T87 Cooling
Anticipator resistor

Summary of content (1 pages)