User Guide

SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
3 63-2188—4
Fig. 1. Series 61 and 62 Modutrol IV Motor mounting dimensions in in. (mm).
Electrical Ratings: See Table 2.
Table 2. Series 61 and 62 Modutrol IV Motor
Power Consumption Ratings.
Auxiliary Switch Ratings: See Table 3.
Table 3. Auxiliary Switch Ratings.
a
40 VA pilot duty, 120/240 Vac on opposite contact.
Control Inputs:
Floating three-wire (Series 60): drive open, hold, drive closed.
Series 62 models include an internal, electrically isolated
feedback potentiometer that provides shaft position
indication.
M17089BB
4-7/8
(124)
5-1/2
(140)
13/16
(20)
4-1/16 (103)
1/4
(7)
1-1/2 (37)
4-1/16 (103)
4-1/16 (103)
WIRING
BOX
MOTOR
AUXILARY
END
POWER
END
ADAPTER
BRACKET
2-9/16
(66)
5-3/8
(137)
6-7/16
(164)
9/16 (15)
3/4
(19)
TOP VIEW OF BRACKET TOP VIEW
4-5/8
(116)
4-1/4
(107)
2-5/16
(58)
11/16
(17)
4-7/8 (124)
5-9/16 (141)
1/4 (7)
5-13/16
(148)
2
POWER END
1
3
4
5
1-1/2 (37)
3/4
(19)
SPRING RETURN MODEL SHOWN
SOME MODELS DO NOT HAVE AN AUXILIARY
SHAFT. ALL OTHER DIMENSIONS ARE THE SAME.
FOR HIGH TORQUE (60 LB-IN.) SPRING RETURN
MODELS 8-3/4 (222); FOR LOW TORQUE (25 LB-IN.)
SPRING RETURN MODELS 8-1/4 (210);
NON-SPRING RETURN MODELS 7-5/16 (185).
FOR HIGH TORQUE (60 LB-IN.) SPRING
RETURN MODELS (SHOWN).
FOR LOW TORQUE (25 LB-IN.) SPRING
RETURN MODELS.
FOR NON-SPRING RETURN MODELS.
1
2
3
4
5
Internal
Transformer
Voltage at
50/60 Hz
Power Consumption
Non-Spring
Return
Spring
Return
(VA) (W) (VA) (W)
No 24 17 15 21 20
Yes 24 26203025
120 26203025
208 26203025
240 27203425
Single Contact
Rating
a
120V (in Amps) 240V (in Amps)
Full Load 7.2 3.6
Locked Rotor 43.2 21.6