Brochure

424 70-6910
Modutrol IV Motors
M7164 Modutrol IV™ Motors
Series 71 Modutrol IV™ Motors non-spring return motors are used
to control dampers and valves. These motors accept a voltage
signal from an electronic controller to position a damper or valve
at any point between open and closed.
Integral junction box provides NEMA 3 weather protection if motor is
mounted in the upright position
Motor and circuitry operate from 24 Vac
Quick-connect terminals are standard – screw terminal adapter is
available
Adapter bracket for matching shaft height of older motors is available
Motors have eld adjustable stroke (90 to 160 degrees)
Integral auxiliary switches are available factory mounted, or can be
eld added
All models have dual shafts (slotted and tapped on both ends)
All models have auxiliary switch cams
Fixed torque throughout the entire voltage range
Application: Electric
Control Signal: Modulating, 10.5-13.5 Vdc
Frequency: 50 Hz; 60 Hz
Fail Safe Mode: Non-Spring Return
Auxiliary Switch Ratings: AFL - 120 Vac – 7.2A; ALR- 120 Vac –
43.2A; AFL - 240 Vac – 3.6A; ALR- 240 Vac – 21.6A
External Auxiliary Switches Available: Ye s
Shaft Rotation (upon control signal increase): Clockwise (as viewed
from power end) (normally closed)
Electrical Connections: Quick-connect terminals
Mounting: Foot-mounted
Power Consumption: Driving – 10 VA
Timing, Nominal: 30 - 60 sec
Feedback: No
Shaft Dimensions: 0.375 in. Square (10 mm Square)
Motor shafts: 2; Dual-ended shaft
Deadweight Load on Shaft: Either End – 200 lbs.; Combined on both
Shafts – 300 lbs.
Weight: 6.5 lb
Approximate, Dimensions: 6 7/16 in. high x 5 1/2 in. wide x 7 5/16 in.
deep (164 mm high x 140 mm wide x 185 mm deep)
Ambient Temperature Range: -40°F to +150°F (-40°C to +60°C)
Includes: Transformer
Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436,
Guide No. XAPX for USA and Canada
Approvals, CE: EN55011 (Emission) EN50082-2 (Immunity)
73/23/EEC (LVD)
Approvals, RoHS: 2011/65/ES
Accessories:
220736A/U – Internal Auxiliary Switch Assembly - 1 Switch
220736B/U – Internal Auxiliary Switch Assembly - 2 Switches
220738A/UAdapter Bracket. Adjusts shaft height to match Modutrol
III motors
220741A2-71/U – Screw Terminal Adapter Kit for Series 71 Modutrol
IV Series 2 motors - Converts quick-connect terminals to screw
terminals
221455A/U – Innitely adjustable Motor Crank Arm
4074ERU/UWeatherproong kit. Protects motor from driving rain
when mounted in any position. Not needed if motor is mounted
upright.
50017460-001/U – 24/120/230 Vac Internal Transformers for Series 2
Motors
50017460-003/U – 120 Vac Internal Transformers for Series 2 Motors
Material Number Torque Rating
(lb-in.)
Torque Rating
(Nm)
Supply Voltage Internal
Auxiliary Switch
Factory
Stroke Setting
Stroke Internal
Transformer
M7164A1017/U 35 lb-in. 4 Nm 24V; 120V; 230V 0 90 degrees Adjustable; 90 to 160 degrees, Asymmetrical 50004263-001
M7164G1030/U 35 lb-in. 4 Nm 120V 0 90 degrees Adjustable; 90 to 160 degrees, Symmetrical 50004263-003