Install Instructions
Table Of Contents
LP914A AND LP915A PNEUMATIC TEMPERATURE SENSORS 
M18358 
Fig. 4. LP914A wall mounted. 
Well Mount (Water Model) 
A bracket, two speed nuts and two no. 10-24 screws are 
furnished for mounting a water model. See Fig. 5. 
1.  Loosen the screws of the mounting bracket. 
2.  Remove one screw completely and swivel the bracket 
to the side. 
3.  Put the sensing element into the well, which has been 
factory filled with heat conductive compound. 
NOTE:  The compound is evenly distributed when the sens-
ing element is inserted. 
4.  When the sensor is fully into the well, swivel the bracket 
back into position so that the lip fits under the nut head 
of the well. 
NOMINAL 
DIMENSIONS 
LP914 WELLS 
SENSOR DIMENSIONS 
WELL 
IN IN. (MM) 
MATERIAL 
315046A 
15-3/8 (390) 
COPPER 
315046B 
7-3/8 (187) 
COPPER 
315904A 
15-5/16 (389) 
STAINLESS 
315904B 
STEEL
7-5/16 (186) 
M18357 
Fig. 5. LP914A well mounted. 
INSTALLING LP914 INTO AN EXISTING LP902 WELL 
1.  Remove the LP902 from the well. 
2.  Add the 1/2 in. x 3/8 in. brass pipe bushing (part #1697). 
3.  Seal the well with heat conductive compound (part  
#107408). 
4.  Mount the LP914A. See Fig. 6. 
1/2 IN. X 3/8 IN. BRASS 
PIPE BUSHING (NO. 1697) 
WELL 
BRACKET 
LP914 
M18354 
Fig. 6. LP914A mounted in an existing LP902 well. 
LP915A Liquid Filled 
BEFORE INSTALLING 
Mount the sensor element in an accessible location where 
average temperatures can be sensed. See Fig. 7 and 8. 
NOTE:   When used as a discharge-air or mixed-air controller, 
mount the element downstream from the heating coil 
or mixing dampers to ensure reasonable mixing of 
the air before the temperature is measured. 
1.  Use the three no. 10 sheet metal screws and gasket to 
mount the LP915A. 
2.  Use the 314439 capillary clips (order separately) to 
install an averaging element. See Fig. 9. 
GASKET 
CAPILLARY 
#10 MOUNTING 
SCREWS (3) 
M18359 
Fig. 7. LP915A duct mounted. 
95-5527EF  2 