Install Instructions
Table Of Contents
LP914A and LP915A 
Pneumatic Temperature Sensors 
INSTALLATION INSTRUCTIONS 
DESCRIPTION 
The LP914A and LP915A Pneumatic Temperature Sensors 
are used with the RP908 or RP920 controllers to provide 
proportional control of pneumatic valve or damper actuators. 
CAUTION 
Equipment Damage Hazard. 
•  Do not remove the cover of the sensor or tamper 
with the sensor. 
•  Be careful not to dent or damage the sensor. 
•  Do not mount the LP914A or LP915A Pneumatic 
Temperature Sensor on surfaces that overlap. 
INSTALLATION 
LP914A Rod and Tube 
Duct Mount 
Two no. 10 sheet metal screws and a gasket are furnished to 
mount the LP914A in the duct. See Fig. 1 and 2. The sensing 
element needs a 1 in. (25mm) hole. 
GASKET 315182 
M18351 
Fig. 1. LP914A duct mounted. 
® U.S. Registered Trademark 
Copyright © 2002 Honeywell •  All Rights Reserved 
2-1/2 (64) 
7  or  15 
(178 or 381) 
2 
(51) 
1 
(25) 
11/32 
(9) 
2-29/32 
(74) 
M18352 
Fig. 2. LP914A dimensions in In. (mm). 
Through Wall Mount 
The master version of the LP914A can be mounted in any wall 
up to 12 in. (305mm) thick. See Fig. 3 and 4. 
1.  Prepare a 5/8 in. (16mm) hole for the sensing element. 
2.  Insert the sensing element. 
3.  Attach the sun shade from the opposite side of the wall. 
4.  Use the small set screw to fix the position of the sensing 
element through the wall. 
5.  Check the sun shade position and tighten the set screw 
on the mounting bracket. 
NOTE:  The sensor mounting bracket has two 1/4 in. (6mm) 
holes for fastening to the wall. When the wall in thin, 
the head of the sensor can protrude slightly into the 
room. 
2-1/2 
1/2 (13) DIA. 
(64) 
7/16 
(11) 
1-1/2 
(38) 
1/4 (6) DIA. 
3 (76) 
M18353 
Fig. 3. LP914A wall model mounting bracket. 
95-5527E
F 