User Guide
INCOMM L510 LAMP CONTROLLER USER GUIDE
7 31-00593-01
The thermostat will display “rid” when it has entered Service Parameter mode.
2. If not already done, set the required Room ID, PAN ID, and RF Channel into the e7/e7w. These values will be transferred to
the L510 when you initiate the Bind. If this is already set, skip to Step 3.
Set the Room ID:
a. Press Mode when the rid is displayed. The currently stored Room ID value is displayed and will begin scrolling across the
screen one numerical setting at a time, from highest to lowest (left most to right most value). Note that the five-digit
number comprises three fields: highest digit, middle two digits, and lowest two digits.
b. Scrolling will first stop at the highest digit and display three vertical dots. Use the UP/DOWN arrow buttons to change
this value (range is 0-6). Press FAN to continue.
c. It will display two middle digits and two vertical dots. Set the middle two values using the UP/DOWN arrow buttons
(range is 0-99). Press FAN to continue.
d. It will display the last two digits and a single dot. Set the previous two digits using the UP/DOWN arrow buttons (range is
0-99). Press MODE to accept the value.
e. The new ID number displays across the display. The E528/E527 stores the value in the memory beeps. The E529 does
not beep. It will show rid again once the scrolling is complete.
Set the PAN ID:
The valid ID range is 0-255; refer to the property-specific documentation for applicable PAN ID settings. To set the PAN ID, do the
following:
a. Use the UP/DOWN arrow buttons to select PAN.
b. Press MODE
c. Use the UP/DOWN arrow buttons to select the valid PAN ID value.
d. Press FAN to store the value in memory.