Troubleshooting Guide

13
Cause of Error
Cause: The outdoor unit control panel will indicate “exhaust
sensor error” and send it to the main internal control panel
when it detects short circuit or open circuit of the exhaust
sensor.
Inspection path: Exhaust sensor Sensor wire
Connectors
Main external control panel
Tools Required
Multimeter, 50K standard exhaust sensor
Possible Broken Part
Exhaust sensor,outdoor unit controlpanel
Troubleshooting
Procedures
1. Check if there is any evident resistance problem in the
sensor. if in short circuit or open circuit, the resistance
should maintain in a reasonable range (about 50K when
the compressor is not working and between 3 Kand 30
Kafter the compressor works for a while, the
corresponding exhaust temperature should be
100-38).
2. Check if the sensor wire or the sensor connecting wire is
damaged.
3. Check if the connecting terminal is connected firmly, the
weld between the terminal and the main control panel is
loose; pull the terminal slightly for inspection if
necessary.
4. Check if the sensor is damp/wet. The coil sensor is quite
easy to be damp/wet in case the lead wire of coil sensor
is above the copper pipe.
5. If there is no standard sensor at hand, exchange the
exhaust sensor with the one beside it to see if the error
changes. If yes, there is something wrong with the sensor
and it should be replaced; if it still indicates
“external coil sensor error”, replace the outdoor unit
control panel.
Key Details
DO NOT USE A SENSOR WITH A VALUE LOWER OR HIGHER
THAN 50K
F4 EXHAUST SENSOR ERROR