User Guide
ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Honeywell • 37
Standard Object Types Supported:
Honeywell SmartVFD HVAC/SmartDrive HVAC product family supports:
• Device Object
• Analog Value Object
• Binary Value Object
The Analog Values that are commandable contain the priority array and relinquish default
properties. All Analog Values that are not commandable become writable when the out of ser-
vice property is set to true.
The Binary Values that are commandable contain the priority array and relinquish default prop-
erties. All Binary Values that are not commandable become writable when out of service prop-
erty is set to true.
Device Object
Object property Readable Writable
object-identifier x
object-name x
object-type x
system-status x
vendor-name x
vendor-identifier x
model-name x
firmware-revision x
application-software-version x
description x
protocol-version x
protocol-revision x
protocol-services-supported x
protocol-object-types-supported x
object-list x
max-apdu-length-accepted x
segmentation-supported x
max-segments-accepted x
local-time x
local-date x
apdu-segment-timeout x
apdu-timeout x
number-of-apdu-retries x
max-master x
max-info-frames x
device-address-binding x
database-revision x
active-cov-subscriptions x