6.6 Processdata mapping in drive application
The drive application allows you to choose freely which data is mapped into processdata out
objects. See the drive appllication 'Fieldbus DataMap' parameters (P3.6).
Some of the drive processdata values are available in BACnet analog value object and some
are available via binary value objects.
fb_ProcessdataOut_01 BV7 - BV14 and AV15
fb_ProcessdataOut_02 - 08 AV16 - AV22
If binary coded data needs to be produced over BACnet, we recommend to use
‘fb_ProcessdataOut_01’ which is available via BV objects. Note that ‘fb_ProcessdataOut_01’
is also available via AV15 object but we recommend to use it only when an analog value is
mapped into ‘fb_ProcessdataOut_01’. Follow the same principle with ‘fb_ProcessdataOut_01’
– ‘fb_ProcessdataOut_08’ which are available in AV objects 16-22.