User Guide

Honeywell • 38 ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE
Analog Value Object
Binary Value Object
Analog Value Object - Commandable
Object property Readable Writable Commandable
object-identifier x
object-name x
object-type x
present-value x x
status-flags x
event-state x
out-of-service x x
units x
priority-array x
relinquish-default x x
cov-increment x x
Analog Value Object - writable when out-of-service is set true
Object property Readable Writable
object-identifier x
object-name x
object-type x
present-value x
* x Normally ‘read only’ but
becomes writable when out-of-
service set to true
status-flags x
event-state x
out-of-service x x
units x
cov-increment x x
Binary Value Object - Commandable
Object property Readable Writable Commandable
object-identifier x
object-name x
object-type x
present-value x x
status-flags x
event-state x
out-of-service x x
priority-array x