User Guide

SMARTVFD HVAC
63-4520—08 4
Table 4. SmartVFD HVAC Technical Specifications.
Mains connection Input voltage U
in
208...240V; 380…480V; -10%…+10%
Input frequency 47…66 Hz
Connection to mains Once per minute or less
Starting delay 4 s (Frame4 to Frame6); 6 s (Frame7 to Frame9)
Motor connection Output voltage 0-U
in
Continuous output current I
L
:Ambient temperature max. +104°F, overload 1.1 x I
L
(1 min./10 min.)
Starting current I
S
for 2 s every 20 s
Output frequency 0…320 Hz (standard)
Frequency resolution 0.01 Hz
Control
characteristics
Switching frequency (see
parameter M3.1.2.1)
1.5…10 kHz;
Defaults: 6 kHz (Frame4-6), 4 kHz (Frame7), 3 kHz (Frame8-9)
Automatic switching frequency derating in case of overheating.
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 8…320 Hz
Acceleration time 0.1…3000 sec
Deceleration time 0.1…3000 sec
Ambient conditions Ambient operating temperature Frame4-Frame9:
I
L
: 14°F (no frost)…+104°F
Storage temperature -40°F…+158°F
Relative humidity 0 to 95% R
H
, non-condensing, non-corrosive
Air quality:
chemical vapors
mechanical particles
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 3,280 ft. (1,000 m)
1-% derating for each 328 ft. (100 m) above 3,280 ft. (1,000 m)
Max. altitudes:
208...240V: 14,764 ft. (4,500 m) (TN and IT systems)
380...480V: 9,842 ft. (TN and IT systems)
Vibration
EN61800-5-1/
EN60068-2-6
5…150 Hz
Displacement amplitude 1 mm (peak) at 5…15.8 Hz
(Frame4…Frame9) Max acceleration amplitude 1 G at 15.8…150 Hz
(Frame4…Frame9)
Shock
EN61800-5-1
EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
Enclosure class IP21/NEMA 1 standard in entire kW/HP range IP54/NEMA12 option
Notel Keypad required for IP54/NEMA12
EMC (at default
settings)
Immunity Fulfils EN61800-3 (2004), first and second environment
Emissions Depend on EMC level.
+EMC2: EN61800-3 (2004), Category C2 Honeywell Smart VFD HVAC
will be delivered with class C2 EMC filtering, if not otherwise specified.
Honeywell Smart VFD HVAC can be modified for IT-networks.
Emissions Average noise level (cooling fan)
sound power level in dB(A)
Frame4: 65 Frame7: 77
Frame5: 70 Frame8: 86
Frame6: 77 Frame9: 87
Safety EN 61800-5-1 (2007), CE, cUL; (see unit nameplate for more detailed
approvals)