User Guide
Table Of Contents
- 1. Safety
 - 2. Modbus - general info
 - 3. Modbus technical data
 - 4. Modbus installation
 - 5. Programming
 - 5.2.1 Ethernet common settings (M5.8.1)
 - 5.2.2 Modbus TCP settings (M5.8.2)
 - 5.3.1 Modbus RTU Parameters
 - 5.3.2 Modbus RTU monitoring values
 - 5.4.1 Ethernet common settings
 - 5.4.2 Modbus TCP settings
 - 5.4.2.1 Common settings
 - 5.4.3 Modbus TCP monitoring values
 - 5.4.3.1 Connection 1
 - 5.4.3.2 Connection 2
 - 6.3.1 Coil registers
 - 6.3.2 Input discrete registers
 - 6.3.3 Holding and input registers
 - 6.3.3.1 Drive Application ID’s
 - 6.3.3.2 FB Process data IN
 - 6.3.3.3 FB Process data OUT
 - 6.3.3.4 ID map
 - 6.3.3.5 Operation day counter
 - 6.3.3.6 Resettable operation day counter
 - 6.3.3.7 Energy counter
 - 6.3.3.8 Resettable energy counter
 - 6.3.3.9 Fault history
 
Modbus installation Honeywell • 13
7
Unless already done for the other control cables,
cut free the opening on the AC drive cover for
the RS485 cable (protection class IP21).
8
Remount the AC drive cover and run the RS485
cables as shown in picture.
NOTE:  When planning the cable runs, remem-
ber to keep the distance between the fieldbus
cable and the motor cable at a minimum of 30
cm.
9
The bus termination must be set for the first and the last device of the fieldbus
line. See picture below. See also step 6 on page 12. We recommend that the first
device on the bus and, thus, terminated was the Master device.
RS485
cables
Fieldbus
= Bus termination
Termination
activated
Termination
activated
 with
DIP switch
Termination
deactivated
Drive Drive Drive Drive Drive