Quick setup Honeywell • 37
8. Quick setup
Following these instructions, you can easily and fast set up your Modbus for use:
1
Choose control place.
A. Press LOC/REM button on keypad to select 
Remote Control Place
B. Select Fieldbus as remote control place: 
 Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15) > FieldbusCTRL
2
Make these settings in the master software
C. Set Control Word to ‘0’ (2001)
D. Set Control Word to 
‘
1’
 (2001)
E. Drive status is RUN
F. Set Reference value to ‘5000’ (50.00%) (2003).
G. Actual speed is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
H. Set 
Control Word to ‘0’ (2001)
I. Drive status is STOP.