User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
62 Parameter Descriptions Honeywell
10
10.3 FREQUENCY REFERENCES (CONTROL PANEL: MENU PAR -> P3)
3.3 I/O REFERENCE
Defines the selected frequency reference source when the drive is controlled
from the I/O terminal.
0 = Preset speed 0 - 7
1 = Keypad reference
2 = Reference from Fieldbus (FBSpeedReference)
3 = AI1 reference (terminals 2 and 3, e.g. potentiometer)
4 = AI2 reference (terminal 4 and 5, e.g. transducer)
3.4 - 3.11 PRESET SPEEDS 0 - 7
These parameters can be used to determine frequency references that are ap-
plied when appropriate combinations of digital inputs are activated. Preset
speeds can be activated from digital inputs despite of the active control place.
Parameter values are automatically limited between the minimum and maxi-
mum frequencies. (par. 3.1, 3.2).
10.4 RAMPS & BRAKES SETUP (CONTROL PANEL: MENU PAR -> P4)
4.1 RAMP SHAPE
The start and end of the acceleration and deceleration ramp can be smoothed
with this parameter. Setting value 0 gives a linear ramp shape which causes
acceleration and deceleration to act immediately to the changes in the refer-
ence signal.
Speed Preset
speed B2
Preset
speed B1
Preset
speed B0
If P3.3 = 0,
Preset speed 0
Preset speed 1 x
Preset speed 2 x
Preset speed 3 x x
Preset speed 4 x
Preset speed 5 x x
Preset speed 6 x x
Preset speed 7 x x x
Table 10.1: Preset speeds 1 - 7