User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
Honeywell Parameters 55
9
9.12 EASY USAGE MENU (CONTROL PANEL: MENU PAR -> P0)
9.13 SYSTEM PARAMETERS
Code Parameter Min Max Unit Default ID Note
P13.1
Parameter
conceal
01 1 115
0 = All parameters visible
1 = Only quick setup
parameter group visible
P13.2 Drive setup 0 3 0 540
0 = Basic
1 = Pump drive
2 = Fan drive
3 = Conveyor drive (HP)
NOTE! Visible only duri-
ing Startup wizard
Table 9.12: Easy usage menu parameters
Code Parameter Min Max Default Note
Software information (MENU PAR -> S1)
S1.1 Software package
S1.2 Power SW version
S1.3 API SW version
S1.4 API Firmware interface
S1.5 Application ID
S1.6 Application revision
S1.7 System load
RS485 information (MENU PAR -> S2)
S2.1 Communication status
Format: xx.yyy
xx = 0 - 64 (Number of error
messages)
yyy = 0 - 999 (Number of
correct messages)
S2.2 Fieldbus protocol 0 1 0 0 = FB disabled 1= Modbus
S2.3 Slave address 1 255 1
S2.4 Baud rate 0 5 5
0=300, 1=600, 2=1200,
3=2400, 4=4800, 5=9600,
S2.5 Number of stop bits 0 1 1 0=1, 1=2
S2.6 Parity type 0 0 0 0= None (locked)
S2.7 Communication time-out 0 255 10
0= Not used, 1= 1 second,
2= 2 seconds, etc.
Table 9.13: System parameters