9.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P12.1 PI activation 0 2 0 163
0 = Not used
1 = PI for motor control
2 = PI for external use
P12.2 PI controller gain 0.0 1000 % 100.0 118
P12.3
PI controller I-
time
0.00 320.0 s 10.00 119
P12.4
Keypad PI refer-
ence
0.0 100.0 % 0.0 167
P12.5 Setpoint source 0 3 0 332
0 = Keypad PI reference,
P12.4
1 = Fieldbus
2 = AI1 Only in API FULL
& LIMITED
3 = AI2 Only in API FULL
P12.6 Feedback source 0 2 2 334
0= Fieldbus
1 = AI1 Only in API FULL
& LIMITED
2 = AI2 Only in API FULL
P12.7
Feedback mini-
mum
0.0 100.0 % 0.0 336 0 = No minimum scaling
P12.8
Feedback maxi-
mum
0.0 100.0 % 100.0 337
100,0 = No maximum scal-
ing
P12.9
Error value inver-
sion
0 1 0 340
0=No inversion (Feed-
back<Setpoint->Increase
PI Output)
1=Inverted (Feedback<Set-
point->Decrease PI Output)
Table 9.11: PI control parameters