User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
54 Parameters Honeywell
9
9.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P12.1 PI activation 0 2 0 163
0 = Not used
1 = PI for motor control
2 = PI for external use
P12.2 PI controller gain 0.0 1000 % 100.0 118
P12.3
PI controller I-
time
0.00 320.0 s 10.00 119
P12.4
Keypad PI refer-
ence
0.0 100.0 % 0.0 167
P12.5 Setpoint source 0 3 0 332
0 = Keypad PI reference,
P12.4
1 = Fieldbus
2 = AI1 Only in API FULL
& LIMITED
3 = AI2 Only in API FULL
P12.6 Feedback source 0 2 2 334
0= Fieldbus
1 = AI1 Only in API FULL
& LIMITED
2 = AI2 Only in API FULL
P12.7
Feedback mini-
mum
0.0 100.0 % 0.0 336 0 = No minimum scaling
P12.8
Feedback maxi-
mum
0.0 100.0 % 100.0 337
100,0 = No maximum scal-
ing
P12.9
Error value inver-
sion
0 1 0 340
0=No inversion (Feed-
back<Setpoint->Increase
PI Output)
1=Inverted (Feedback<Set-
point->Decrease PI Output)
Table 9.11: PI control parameters