User Guide

Table Of Contents
Honeywell Parameters 53
9
9.10 AUTORESTART PARAMETERS (CONTROL PANEL: MENU PAR ->
P10 )
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P10.1 Wait time 0.10 10.00 s 0.50 717
Delay before automatic
restart after a fault has dis-
appeared
P10.2 Trial time 0.00 60.00 s 30.00 718
Defines the time before the
frequency converter tries to
automatically restart the
motor after the fault has dis-
appeared
P10.3 Start function 0 2 0 719
0 = Ramp
1 = Flying start
2 = According to P4.2
P10.4 Automatic restart 0 1 0 731
0 = Disabled
1 = Enabled
Table 9.10: Autorestart parameters