9.9 PROTECTIONS (CONTROL PANEL: MENU PAR -> P9)
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P9.1
Response to 4mA
reference fault
0 2 1 700
0 = No response
1 = Warning
2 = Fault, stop acc. to
P2.3
P9.2
Response to
under voltage
fault
0 2 2 727
P9.3
Ground fault pro-
tection
0 2 2 703
P9.4 Stall protection 0 2 0 709
P9.5
Underload protec-
tion
0 2 0 713
P9.6 Reserved
P9.7
Thermal protec-
tion of the motor
0 2 0 704
P9.8
Motor ambient
temperature
-20 100
Fahre-
heit (C)
40 705
P9.9
Motor cooling fac-
tor at zero speed
0,0 150.0 % 40.0 706
P9.10
Motor thermal
time constant
1 200 min 45 707
Table 9.9: Protections