User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
50 Parameters Honeywell
9
9.7 ANALOGUE INPUTS (CONTROL PANEL: MENU PAR -> P6)
9.8 DIGITAL AND ANALOGUE OUTPUTS (CONTROL PANEL: MENU PAR -
> P7)
Code Parameter Min Max Unit Default ID Note
Only in API FULL & LIMITED
P6.1 AI1 Signal range 0 3 0 379
API FULL and LIM-
ITED:
0 = Voltage 0…10 V
1 = Voltage 2…10 V
API LIMITED ONLY:
2 = Current 0…20 mA
3 = Current 4…20 mA
NOTE: When using API
LIMITED, select the
voltage/current range
also with the dip switch
P6.2 AI1 filter time 0.0 10.0 s 0.1 378 0 = no filtering
P6.3 AI1 Custom min -100.0 100.0 % 0.0 380 0.0 = no min scaling
P6.4 AI1 Custom max -100.0 100.0 % 100.0 381 100.0 = no max scaling
Only in API FULL
P6.5 AI2 signal range 2 3 3 390
2 = Current 0…20 mA
3 = Current 4…20 mA
P6.6 AI2 filter time 0.0 10.0 s 0.1 389 0 = no filtering
P6.7 AI2 Custom min -100.0 100.0 % 0.0 391 0.0 = no min scaling
P6.8 AI2 Custom max -100.0 100.0 % 100.0 392 100.0 = no max scaling
Table 9.7: Analoque inputs
Code Parameter Min Max Unit Default ID Selections
Only in API FULL
P7.1
Relay output 1
content
0 8 2 313
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault Inverted
5 = Warning
6 = Reversed
7 = At Speed
8 = Motor Regulator
Active
In all API versions
Table 9.8: Digital and analogue outputs