50 Parameters Honeywell
9
9.7 ANALOGUE INPUTS (CONTROL PANEL: MENU PAR -> P6)
9.8 DIGITAL AND ANALOGUE OUTPUTS (CONTROL PANEL: MENU PAR -
> P7)
Code Parameter Min Max Unit Default ID Note
Only in API FULL & LIMITED
P6.1 AI1 Signal range 0 3 0 379
API FULL and LIM-
ITED:
0 = Voltage 0…10 V
1 = Voltage 2…10 V
API LIMITED ONLY:
2 = Current 0…20 mA
3 = Current 4…20 mA
NOTE: When using API
LIMITED, select the
voltage/current range
also with the dip switch
P6.2 AI1 filter time 0.0 10.0 s 0.1 378 0 = no filtering
P6.3 AI1 Custom min -100.0 100.0 % 0.0 380 0.0 = no min scaling
P6.4 AI1 Custom max -100.0 100.0 % 100.0 381 100.0 = no max scaling
Only in API FULL
P6.5 AI2 signal range 2 3 3 390
2 = Current 0…20 mA
3 = Current 4…20 mA
P6.6 AI2 filter time 0.0 10.0 s 0.1 389 0 = no filtering
P6.7 AI2 Custom min -100.0 100.0 % 0.0 391 0.0 = no min scaling
P6.8 AI2 Custom max -100.0 100.0 % 100.0 392 100.0 = no max scaling
Table 9.7: Analoque inputs
Code Parameter Min Max Unit Default ID Selections
Only in API FULL
P7.1
Relay output 1
content
0 8 2 313
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault Inverted
5 = Warning
6 = Reversed
7 = At Speed
8 = Motor Regulator
Active
In all API versions
Table 9.8: Digital and analogue outputs