- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
48 Parameters Honeywell
9
9.5 RAMPS AND BRAKES SETUP (CONTROL PANEL: MENU PAR -> P4)
9.6 DIGITAL INPUTS (CONTROL PANEL: MENU PAR -> P5)
Code Parameter Min Max Unit Default ID Note
P4.1 Ramp shape 0.0 10.0 s 0.0 500
0 = Linear
>0 = S-curve ramp time
P4.2 Acceleration time 0.1 3000 s 1.0 103
P4.3 Deceleration time 0.1 3000 s 1.0 104
P4.4
DC braking cur-
rent
Unit
dep.
Unit
dep.
A Varies 507
P4.5
DC braking time
at start
0.00 600.00 s 0 516
0 = DC brake is off at
start
P4.6
Frequency to start
DC braking during
ramp stop
0.10 10.00 Hz 1.50 515
P4.7
DC braking time
at stop
0.00 600.00 s 0 508
0 = DC brake is off at
stop
Table 9.5: Motor control parameters
Code Parameter Min Max Unit Default ID Note
P5.1 Start signal 1 0 6 1 403
0 = Not used
1 = DI1
2 = DI2 Only in API
FULL & LIMITED
3 = DI3
4 = DI4 Only in API
FULL
5 = DI5
6 = DI6
P5.2 Start signal 2 0 6 2 404 As parameter 5.1
P5.3 Reverse 0 6 0 412 As parameter 5.1
P5.4 Ext. fault Close 0 6 0 405 As parameter 5.1
P5.5 Ext. fault Open 0 6 0 406 As parameter 5.1
P5.6 Fault reset 0 6 5 414 As parameter 5.1
P5.7 Run enable 0 6 0 407 As parameter 5.1
P5.8 Preset speed B0 0 6 3 419 As parameter 5.1
P5.9 Preset speed B1 0 6 4 420 As parameter 5.1
Table 9.6: Digital inputs