9.3 START/STOP SETUP (CONTROL PANEL: MENU PAR -> P2)
9.4 FREQUENCY REFERENCES (CONTROL PANEL: MENU PAR -> P3)
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P2.1 Control place 1 3 1 125
1 = I/O terminal
2 = Keypad
3 = Fieldbus
P2.2 Start function 0 1 0 505
0 = Ramp
1 = Flying start
P2.3 Stop function 0 1 0 506
0 = Coasting
1 = Ramp
P2.4
Start/Stop
logic
0 3 0 300
DI1 DI2
0 Start Fwd Start reverse
1 Start Reverse
2
Start Pulse Stop Pulse
3 Start Fwd Start Rv
REAF REAF
Table 9.3: Start/stop setup
Code Parameter Min Max Unit Default ID Note
P3.1 Min frequency 0.00 P3.2 Hz 0.00 101
P3.2 Max frequency P3.1 320 Hz 50.00 102
P3.3 I/O reference 0 4 3 117
0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1 (API FULL &
LIMITED)
4 = AI2
(API FULL)
P3.4 Preset speed 0 0.00 P3.2 Hz 5.00 124 Activated by digital inputs
P3.5 Preset speed 1 0.00 P3.2 Hz 10.00 105 Activated by digital inputs
P3.6 Preset speed 2 0.00 P3.2 Hz 15.00 106 Activated by digital inputs
P3.7 Preset speed 3 0.00 P3.2 Hz 20.00 126 Activated by digital inputs
P3.8 Preset speed 4 0.00 P3.2 Hz 25.00 127 Activated by digital inputs
P3.9 Preset speed 5 0.00 P3.2 Hz 30.00 128 Activated by digital inputs
P3.10 Preset speed 6 0.00 P3.2 Hz 40.00 129 Activated by digital inputs
P3.11 Preset speed 7 0.00 P3.2 Hz 50.00 130 Activated by digital inputs
Table 9.4: Frequency references