User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
44 Parameters Honeywell
9
9.1 QUICK SETUP PARAMETERS (VIRTUAL MENU, SHOWS WHEN PAR.
13.1 = 1)
Code Parameter Min Max Unit Default ID Note
P1.1
Motor nominal
voltage
180 500 V
230
400
110
Check rating plate on the
motor
P1.2
Motor nom. fre-
quency
30 320 Hz 60.00 111
Check rating plate on the
motor
P1.3
Motor nominal
speed
300
2000
0
rpm 1440 112
Default applies for a 4-
pole motor.
P1.4
Motor nominal
current
0.2 x
I
Nunit
1.5 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor
P1.5
Motor cos
0.30 1.00 0.85 120
Check rating plate on the
motor
P1.7 Current limit
0.2 x
I
Nunit
2 x
I
Nunit
A
1.5 x
I
Nunit
107
P1.15 Torque boost 0 1 0 109
0 = Not used
1 = Used
P2.1 Control place 1 3 1 125
1 = I/O terminal
2 = Keypad
3 = Fieldbus
P2.2 Start function 0 1 0 505 0 = Ramp 1 = Flying start
P2.3 Stop function 0 1 0 506 0 = Coasting 1 = Ramp
P3.1 Min frequency 0.00 P3.2 Hz 0.00 101
P3.2 Max frequency P3.1 320 Hz 50.00 102
P3.3 I/O reference 0 4 3 117
0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1 (A PI FULL &
LIMITED)
4 = AI2
(API FULL)
P3.4 Preset speed 0 0.00 P3.2 Hz 5.00 124
Activated by digital
inputs
P3.5 Preset speed 1 0.00 P3.2 Hz 10.00 105
Activated by digital
inputs
P3.6 Preset speed 2 0.00 P3.2 Hz 15.00 106
Activated by digital
inputs
P3.7 Preset speed 3 0.00 P3.2 Hz 20.00 126
Activated by digital
inputs
P4.2 Acceleration time 0.1 3000 s 1.0 103
Acceleration time from 0
Hz to maximum fre-
quency
Table 9.1: Quick setup parameters
ϕ