User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
38 Control Panel Honeywell
8
8.4.3 Monitoring menu
Figure 8.4: Monitoring menu display
Monitoring values mean actual values of measured signals as well as statuses of
some control settings. They are visible in API Full and Limited display, but they can-
not be edited. The monitoring values are listed in Table 8.1.
Pushing the navigation wheel once in this menu takes the user to the next level,
where the monitoring value, e.g. M1.11 and value are visible (see Figure 8.2). The
monitoring values can be browsed by rolling the navigation wheel clockwise, as
shown in Figure 8.4.
Code Monitoring signal Unit ID Description
M1.1 Output frequency Hz 1 Frequency to the motor
M1.2 Frequency reference Hz 25
M1.3 Motor shaft speed rpm 2 Calculated motor speed
M1.4 Motor current A 3 Measured motor current
M1.5 Motor torque % 4
Calculated actual/nominal
torque of the motor
M1.6 Motor power % 5
Calculated actual/nominal
power of the motor
Table 8.1 : SmartVFD Compact monitoring signals
Hz
FAULTALARMSTOPREADY RUN
REF
MON
PAR
FLT
FWD REV I/O KEYPAD BUS
Alternates
in the display
Browse
M1.1 - M1.20