User Guide

Table Of Contents
32 API Honeywell
7
7.2 CONTROL I/O
Terminal
Signal Factory preset Description
1
+10Vre Ref. voltage out Maximum load 10 mA
2
AI1 Analog signal in 1
Freq. reference
P)
0 - +10 V Ri = 200 k
(min)
3
GND I/O signal ground
6
24Vout 24V output for DI's
%, max. load 50
mA
7
GND I/O signal ground
8
DI1 Digital input 1
Start forward
P)
0 - +30 V Ri = 12 k min
9
DI2 Digital input 2
Start reverse
P)
10
DI3 Digital input 3
Preset speed B0
P)
A
A RS485 signal A FB Communication
B
B RS485 signal B FB Communication
4
AI2 Analog signal in 2
PI actual value
P)
0(4) - 20 mA, Ri = 200
5
GND I/O signal ground
13
GND I/O signal ground
14
DI4 Digital input 4
Preset speed B1
P)
0 - +30 V Ri = 12 k (min)
15
DI5 Digital input 5
Fault reset
P)
16
DI6 Digital input 6
Disable PI contr.
P)
18
AO
Output frequency
P)
0(4) - 20 mA, RL = 500
20
DO Digital signal out
Active = READY
P)
Open collector, max. load
48V/50mA
22
RO 11 Relay out 1
Active = RUN
P)
Max. switching load:
250Vac/2A or 250Vdc/
0.4A
23
RO 12
24
RO 21 Relay out 2
Active = FAULT
P)
Max. switching load:
250Vac/2A or 250Vdc/
0.4A
25
RO 22
26
RO 23
Table 7.2 : SmartVFD Compact General purpose application default I/O configuration
and connections for API FULL version
P) = Programmable function, see parameter lists and descriptions, chapters 9 and 10.
Ω
20±
Ω
Ω
Ω
Ω
mA
API FULL