Honeywell Fault Tracing 29
6
35
Application fault Application does not function
Contact the distributor
near to you
50
Analogue input I
in
<
4mA (selected signal
range 4 to 20 mA)
Current at the analogue input is
< 4mA
• control cable is broken or
loose
• signal source has failed
Check the current loop
circuitry
51
External fault
Digital input fault. Digital input
has been programmed as exter-
nal fault input and this input is
active.
Check the programming
and the device indicated
by the external fault infor-
mation. Check also the
cabling of this device.
53
Fieldbus fault
The data connection between
the fieldbus Master and the field-
bus of the drive broken
Check installation.
If installation is correct
contact the nearest Hon-
eywell distributor.
Fault
code
Fault name Possible cause Correcting actions
Table 6.1 : Fault codes