User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
Honeywell Installation 17
4
Category C4: The drives of this class do not provide EMC emission protection.
These kinds of drives are mounted in enclosures. NOTE: An external EMC filter is
usually required to fulfil the EMC emission requirements.
Category C4 for IT networks: Frequency converters of this class fulfil the product
standard EN 61800-3 (2004) if intended to be used in IT systems. In IT systems, the
networks are isolated from ground, or connected to ground through high impedance
to achieve a low leakage current. NOTE: if converters are used with other supplies,
no EMC requirements are complied with.
Environments in product standard EN 61800-3 (2004)
First environment: Environment that includes domestic premises. It also includes
establishments directly connected without intermediate transformers to a low-voltage
power supply network which supplies buildings used for domestic purposes.
NOTE: houses, apartments, commercial premises or offices in a residential building
are examples of first environment locations.
Second environment: Environment that includes all establishments other than
those directly connected to a low-voltage power supply network which supplies build-
ings used for domestic purposes.
NOTE: industrial areas, technical areas of any building fed from a dedicated trans-
former are examples of second environment locations.
4.1.4 Changing the EMC protection class from H or L to T
The EMC protection class of SmartVFD Compact frequency converters can be
changed from class H or L to class T by removing the EMC-capacitor disconnect-
ing screw, see figure below.
Note! Do not attempt to change the EMC level back to class H or L. Even if the pro-
cedure above is reversed, the frequency converter will no longer fulfil the EMC re-
quirements of class H/L!