User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
10 Technical Data Honeywell
3
3. TECHNICAL DATA
3.1 SMARTVFD COMPACT TECHNICAL DATA
Dimensions
and weight
Frame
H (in) W (in) D (in) Weight (lb)
MI1 6.1 2.6 3.9 1.2
MI2 7.7 3.5 4.0 1.5
MI3 10.3 3.9 4.3 2.18
Supply
network
SmartVFD Compact (400V) cannot be used with
corner grounded networks
Motor
connection
Output voltage 0 - U
in
Output current Continuous rated current I
N
at ambient tempera-
ture max. 122 ºF (+50 ºC), overload 1.5 x I
N
max.
1min/10min
Ambient
conditions
Ambient operating
temperature
14 °F (-10 °C) (no frost)…122 °F (+50 °C): rated
loadability I
N
Storage tempera-
ture
-40 °F (-40 °C)…+158 °F (+70 °C)
Relative humidity 0…95% RH, non-condensing, non-corrosive, no
dripping water
Altitude 100% load capacity (no derating) up to 3280 ft.
1% derating for each 328 ft above 3280 ft; max.
6560 ft
Enclosure class IP20 (open Chassis), option: NEMA 1
EMC
Immunity Complies with EN50082-1, -2, EN61800-3
Emissions 230V : Complies with EMC category C2 (Honey-
well level H); With an internal RFI filter
400V: Complies with EMC category C2 (Honey-
well level H): With an internal RFI filter
Both: No EMC emission protection (Honeywell
level N): Without RFI filter
Standards
For EMC: EN61800-3,
For safety: UL508C, EN61800-5-1
Certificates
and
manufacturer’s
declarations of
conformity
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
Table 3.1 : SmartVFD Compact technical data