48kW Generator Spec Sheet

HT
4 www.honeywellgenerators .com
45 kW
LIQUID-COOLED GENERATOR SETS
CONTROL FEATURES
• 2-Line Plain Text LCD Display Simple user interface for ease of operation.
• Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger
still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility
fails, transfer to load takes place.
• Programmable start delay between 10-30 seconds Standard
• Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec.
maximum duration).
• Engine Warm-up 5 seconds
• Engine Cool-Down 1 minute
• Starter Lock-out Starter cannot re-engage until 5 sec. after engine
has stopped.
• Smart Battery Charger Standard
• Automatic Voltage Regulation with Over and Under
Voltage Protection
Standard
Interconnections
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard
High Temperature Shutdown Standard
Overcrank Protection Standard
• Safety Fused Standard
Failure to Transfer Protection Standard
Low Battery Protection Standard
50 Event Run Log Standard
Future Set Capable Exerciser Standard
Incorrect Wiring Protection Standard
Internal Fault Protection Standard
Common External Fault Capability Standard
Governor Failure Protection Standard
Single and three phase connections may vary, refer to the owner’s manual for specific connection information.