Submittal Sheet

Table Of Contents
H7625, H7635, H7655 SERIES 2000 HUMIDITY/TEMPERATURE SENSORS
63-4521—01 2
Sensitivity:
0.1%RH.
Interchangeability:
Less than ±3% RH nominal.
Repeatability:
0.5% RH.
Long term drift:
Less than 2% RH drift/5 years.
Table 1. Model Description
Fig. 1. Wall-mount sensor dimensions in in. (mm).
MODEL
NUMBER REPLACES
RH
ACCURACY MOUNTING
TEMPERATURE
SENSOR OUTPUT SIGNAL USED WITH
H7625A2010 H7625A1008 2% ROOM 20K ohm at 77F,
reference 206598"
Selectable
4-20mA, 0-10Vdc,
or 0-5Vdc
T7350, H775, XL50,
XL500, XFC, W7750B/C,
W7753, W7760A/C,
W7761"
H7635A2012 H7635A1006 3%
H7625B2006 H7625B1006 2% DUCT
H7635B2018 H7635B1004 3%
H7655B2014 H7655B1009 5%
H7635C2015 H7635C1002 3% OUTDOOR
H7626A2020 2% ROOM 1097 ohm at 77F T775
H7636A2022 3%
H7626B2024 2% DUCT
H7636B2026 3%
H7656B2029 5%
M31332
9/16 (14)
13/16 (31)
7/8 (22)4 3/16 (122)
2 3/8 (60)
2 3/8 (60)
1 1/2 (38)
3 (76)
STANDARD
UTILITY
CONDUIT
BOX (2 X 4)
MOUNTING
HOLES
7/8 (22)