Fig. 3. Wall Mount Model Dimensions in inches (mm).
SPECIFICATIONS
Table 1. Models.
Table 2. Specifications.
1
One side of transformer secondary is connected to signal
common. Dedicated transformer is recommended.
2
Time for reaching 63% of reading at 25 °C and 1 m/s air-
flow.
3
Long term exposures to conditions outside normal range
or high humidity may temporarily offset the RH reading
(+3%RH after 60 hours).
4
15-30 VDC/24VAC power supply voltage required for
10 volt output.
Model
Humidity
Accuracy Thermistor Type
H7726A2020 2% 1097 Ohm Wall
H7725A2010 2% 20 kOhm Wall
H7736A2022 3% 1097 Ohm Wall
H7735A2012 3% 20 kOhm Wall
H7725A2010-C 2% NIST
Certified
20 kOhm Wall
H7725B2006 2% 20 kOhm Duct
H7725B2006-C 2% NIST
Certified
20 kOhm Duct
H7726B2024 2% 1097 Ohm Duct
H7735B2018 3% 20 kOhm Duct
H7736B2026 3% 1097 Ohm Duct
H7735C2015 3% 20 kOhm Outdoor
5.66
(143.8)
1.69
(42.9)
0.36
(9.0)
3.00
(76.2)
Power supply
AC Supply/
DC Supply
24VAC, 100mA max.
12-30VDC, 50mA max.
Outputs RH
3-wire 0-5V/10V
4
,
3-wire or 2-wire 4-20mA (Selectable)
Output scaling RH 0-100%RH
Thermistor/
RTD
Nominal
resistance @ 25 °C
20 kOhm
1097 kOhm
Media filter
PBT with water vapor-permeable
membrane
Relative
Humidity
Accuracy
2% models: ±2% max 0 to 100% RH,
±1.5% typ 0 to 80% RH @25°C
3% models: ±3% max 0 to 100% RH,
±2% typ 0 to 100% RH @25°C
Resolution 0.01% RH
Hysteresis ±0.8% RH
Repeatability 0.08% RH
Non-linearity Factory linearized <1%RH
Temperature
coefficient
Fully compensated by on-board
sensor
Response time
2
8s
Output update 0.5s
Operating range 0 to 100% RH (non-condensing)
Long term drift <0.25% RH per year
Operating
conditions
3
41 to 140°F
(5 to 60°C)
@ 20-80% RH
Enclosure
Materials ABS/Polycarbonate
Dimensions
Duct/Outdoor: 4.0”h x 4.4”w x 2.1”d
Duct: (+6.8” probe)
Outdoor: (+2.8” Solar Shield)
Wall: 5.66”h x 3.00”w x 0.36”d
(1.69” depth including recessed
components)
Enclosure Rating
Wall/Duct: IP20/NEMA 1
Outdoor: IP20/NEMA 1 *Vent bottom
of enclosure to achieve NEMA 3R
Rating
Unit Temp Rating -40°F to 158°F (-40 to 70°C)