Install Instructions
H7012A HUMIDITY AND H7012B HUMIDITY AND TEMPERATURE ROOM SENSORS
Table 1. Temperature Offset Due to Wire Resistance per
ASSEMBLY
35 ft (10m) between Sensor and Controller:
Place cover on sensor back and slide upward until it locks in
place (Fig. 4).
Wire Size Pt100 BALCO 500
AWG mm2 F C F C
20 0.5 0.324 0.18 0.54 0.3
17 1.0 0.162 0.09 0.27 0.15
15 1.5 0.108 0.06 0.1 0.1
To remove cover, pry gently with screwdriver as shown
(Fig. 5).