Install Instructions

H7012A Humidity and
H7012B Humidity and Temperature
Room Sensors
INSTALLATION
H7012A Humidity and H7012B Humidity and Temperature
Room Sensors mount either directly to the wall using the
template (Fig. 1) or to a 2 in. x 4 in. electrical box using the
adapter (Fig. 2).
Mounting Directly to Wall
Use the template (Fig. 1) or the sensor back to locate
and drill three screw holes. The Number 1 hole
locations are preferred.
Drill the 1/2 in. (13 mm) or larger hole for the wiring
Pull wires through hole and thread wires through
sensor back.
Use three #8 screws to mount the sensor-back to the
wall. Use holes marked 1 or holes marked 2.
INSTALLATION INSTRUCTIONS
Mounting to 2 in. x 4 in. Electrical Box
Feed wires through large opening at top of adaptor
plate.
Use standard 6 x 32 electrical box machine screw to
mount adaptor plate.
Feed wires through sensor back and use No. 8 sheet
metal screw to fasten sensor back to adaptor plate.
WIRING
Wiring Requirements
Use shielded twisted pair wires for sensor wiring. Ground
shield at the controller.
Maximum sensor wire length from sensor to controller: 660 ft
(200m).
Maintain 6 in. (150 mm) spacing between line voltage and
sensor wires.
Use separate transformers for sensor and controller(s).
Connections
Wire the sensor to the controller as shown in Fig. 3.