Installation Manual
9000-0447 Rev. I
Page 41 of 42
Table 6-1 7100 Series Device Types and Functions
# Device Type Physical Response Action in Alarm Condition
1 Ion Sensor
2 Ion Duct Sensor
Ion
3 Photo Sensor
4 Photo Duct Sensor
5 Photo/Thermal
Photo
Smoke
Alarm
6 Thermal Thermal
7
8 Smoke Det
Alarm
9 Manual Station Manual Alarm
10 Plenum Det
11 N.O. Contact
12 Heat Det
13 SubLoop
14 Waterflow Silenceable
15 Beam Det
16 Duct Det
17 FACP Alarm
18 Remote Zone
19 Smoke/Heat
AMM
Alarm
Trips ALARM LED and
ALARM Relay
Trips other outputs per
Day Alarm or Night
Alarm Response, or by
group.
Smoke Alarm may be
verified or PAS;
Manual Alarm may be
PAS.
Alarm condition latches,
trouble condition is
restorable.
20 Supervisory Switch
(Non Latching)
AMM Supervisory NL Alarms and Troubles
restore.
21 Tamper Switch (Latching) Supervisory L
Trips general supervisory
outputs, SUPERVISORY
LED, TROUBLE Relay.
Alarms latch,
Trouble restore.
22 Waterflow NonSilenceable AMM Waterflow NS Same as ALARM but inhibits panel silence.
23 Non-Reporting Actuator
Latch
Alarms latch
24
Non-Reporting Actuator Nonlatch
AMM
25
Non-Reporting Ion Non latch
Ion
26
Non-Reporting Photo Non latch
Photo
Non-Report
Activates group, but
produces no other
response.
Alarms restore
27 Ion Multilevel Ion
28 Photo Multilevel Photo
Multilevel Produces “Alert”, “Action”, or “Alarm” response
depending on global %-of-alarm settings
29 Signal Silence Silence
30 Reset Reset
31 Drill Fire Drill
32 Alarm Acknowledge Alrm Ack
33 Trouble/Supv Acknowledge Trbl/Supv Ack
34 Aux
AMM
Aux
Non-latching
Produces the specified function
35 End-Of-Line AMM EOL Used for address M99 only
36 Silenceable Signal
37 Nonsilenceable Signal
Signal
AOM
Produces “Short” indication
38 Silenceable Contacts
39 Nonsilenceable Contacts
Form C
AOM
(Output)
No “Short” indication
40
49
User-Defined Device Types
AMM
Choice of Alarm,
Supervisory NL,
Tamper L,
Waterflow NS
Per selected response