Installation Manual
9000-0447 Rev. I
Page 39 of 42
[VIEW] 1:Display Log 2: Print Log
[LOG ] 3:Clear Log 4:Sens. Report
1: Opens Show Events Menu.
2: Opens Print Log Menu.
3: Prompts for OK; if accepted, clears the Event Log and resets
panel.
Main
Log
4: Initiates a sensor sensitivity printout.
(Display shows a log entry)
Scrolls through all logged events, beginning with the most recent
event. If user attempts to scroll beyond the end (or beginning) of
the log, End of log is displayed briefly, then the last (or first)
event is redisplayed.
Main
Log
Show Events
Display cannot give instructions, since it contains all the
information about the event being displayed (same as the
display you would see when the event occurred).
[PRINT} 1: All events 2:Last 20
[LOG]
If there is no log printout in progress, starts a printout as shown
above. Once the printout begins, or if a printout is in progress
when this menu is opened, the message and function change to
“3:Abort printout”. Printout starts immediately, not when OK is
pressed.
Main
Log
Print Log
If printout completes while this menu is still open, the text of the
menu doesn’t change until the user presses a key.
[PANEL] Software Last Cfg. Change
[INFO ] V1.2-001 12:23 07/23/99 33
Main
Log
Shows the system software version, time and date of the most
recent change to the configuration program, and number of the
menu used to make the change (i.e., what was changed).