Installation Manual
9000-0447 Rev. I
Page 23 of 42
4.0 Programming/Operation Instructions
4.1 LED Indicators
Table 4-1 LED Indicators
Designation Description Comments
AC Power On (green) Lights to indicate presence of 120/240 VAC input.
Alarm (red) Lights when system is in alarm, flashes until alarm is
acknowledged.
Supervisory (yellow) Lights when supervisory condition exists, flashes until
trouble acknowledge is performed.
System Trouble (yellow) Lights to indicate trouble condition, flashes until
trouble is acknowledged.
Power Fault (yellow) Lights during a LOW or NO Battery condition.
Ground Fault (yellow) Lights to indicate a ground on a field conductor
NAC 1 Silenced (yellow) Lights to indicate that NAC Circuit has been silenced
via the Signal Silence Switch (if programmed as
silenceable).
NAC 2 Silenced (yellow) Lights to indicate that NAC Circuit has been silenced
via the Signal Silence Switch (if programmed as
silenceable).
System Silenced (yellow) Lights when a System Silence has been performed.
Flashes when disabled.
Figure 9 LED Indicators