3.12 7100-D DACT Event Reporting Codes
The 7100-D DACT event reporting codes are shown in Table 3-6 below:
Table 3-6 DACT-E3 Event Reporting Codes
Event SIA Contact ID 4/2 3/1
Fire Alarm (Smoke or Manual Station) FA GGT 1 110 00 GGT 0T 0
Fire Alarm Restored FH GGT 3 110 00 GGT 2T 2
Waterflow Alarm SA GGT 1 113 00 GGT 0T 0
Waterflow Alarm Restored SH GGT 3 113 00 GGT 2T 2
Trouble (except Waterflow or Special AMM) FT GG0 1 373 00 GG0 8T 8
Trouble Restored FJ GG0 3 373 00 GG0 7T 7
Trouble (Waterflow AMM) ST GG0 1 370 00 GG0 8T 8
Trouble Restored (Waterflow AMM) SJ GG0 3 203 00 GG0 7T 7
Trouble (Special AMM) UT GG0 1 370 00 GG0 8T 8
Trouble Restored (Special AMM) UJ GG0 3 370 00 GG0 7T 7
Supervisory / Tamper (Module) SS GGT 1 203 00 GGT 6T 6
Supervisory Restored (Module) SR GGT 3 203 00 GGT 7T 7
PAS/Action/Supervisory (Sensor) FS GGT 1 200 00 GGT 6T 6
PAS/Action/Supervisory Restored (Sensor) FR GGT 3 110 00 GGT 7T 7
Disable (except Waterflow or Special AMM) FB GG0 1 571 00 GG0 8T 8
Disable Restored FU GG0 3 571 00 GG0 7T 7
Disable (Waterflow AMM) SB GG0 1 570 00 GG0 8T 8
Disable Restored (Waterflow AMM) SU GG0 3 570 00 GG0 7T 7
Disable (Special AMM) UB GG0 1 570 00 GG0 8T 8
Disable Restored (Special AMM) UU GG0 3 570 00 GG0 7T 7
AC Fail AT 0 1 301 00 000 8T 8
AC Fail Restored AR 0 3 301 00 000 7T 7
Phone Line 1 Fault LT 1 1 351 00 000 81 8
Phone Line 1 Fault Restored LR 1 3 351 00 0000 71 7
Phone Line 2 Fault LT 2 1 352 00 000 82 8
Phone Line 2 Fault Restored LR 2 3 352 00 000 72 7
Automatic Test (NORMAL) RP 0 1 602 00 000 90 9
Automatic Test (With Exception) RP991 1 602 00 991 91 9
For Contact ID and SIA Formats:
GG = group number assigned to the device, 00-99
(For networked systems, GG = Node number)
T = Type of device or event causing the event to be reported.
0= Non-loop event
1= Any event or device type not listed below
2= Manual Station
3= Supervisory Device (Non-latching)
4= Supervisory Device (Latching)
5= Waterflow (Non-silenceable)
6= Smoke Alarm
8= Multilevel Device
Note:Special AMMs include the following functions:
Reset Switch, Silence Switch, Drill Switch, Alarm Acknowledge Switch, Trouble Acknowledge
Switch.