Installation Manual

9000-0447 Rev. I
Page 17 of 47
3.5 Analog Sensors
The 7100 accommodates only Gamewell-FCI approved, UL Listed, analog sensors and
bases. See the Gamewell-FCI Publication, P/N 9000-0427 for a list of approved sensors
and bases. Each signaling line circuit can accommodate 99 sensor address points, using
Address numbers 01 to 99.
3.5.1 Address Switches
Addresses are set via the rotary switches on each sensor or module. Setting the
address is accomplished by turning each of the two (2) rotary switches until they
point to the numbers indicating the proper address (e.g., SW1 @ #2 and SW2 @
#5 would indicate address #25).
3.5.2 Drift Compensation
The 7100 contains a program which performs continuous testing of analog
sensors, including sensitivity tests. This program will compensate all analog
sensors for age and environmental conditions. Should a problem occur in a
sensor, a “Failed Test”, “Dirty” or “Very Dirty” indication for the specific device will
appear on the system display and be recorded in the Event Log and the Serial
Port.
3.6 Addressable Modules
The 7100 accommodates only Gamewell-FCI approved, U.L. Listed, addressable monitor
and/or control modules. See the Gamewell-FCI Compatibility Addendum, P/N 9000-0427
for a list of approved modules. Each SLC can accommodate 98 addressable module
points, using Addresses 101 through 198.
In the event of common mode noise problems, a Noise Control Module (NCM-1) may be
installed. See Figure 7. The white wire lead must be connected to earth ground.
3.6.1 Address Switches
These addresses are set via the rotary switches on each module. Setting the
address is accomplished by turning each of the two (2) rotary switches until they
point to the numbers indicating the proper address (e.g., SW1 @ #5 and SW2 @
#7 would indicate address # 157). Note that the “100" digit is pre-set in all
addressable modules.
3.7 Deleted.
3.8 Deleted.
IMPORTANT: In systems incorporating the Positive Alarm Sequence (PAS)
in conjunction with addressable modules, (AMM-2F, -4F, -4SF), only one (1)
initiating device may be connected to each module (address).
EXAMPLE: Connect only one manual station per AMM-2F module.