Installation Manual

9000-0447 Rev. I
Page 5 of 42
1.2.2 Optional Features
Class A Module (CAOM) with Disconnect Switches for NACs and SLCs
Digital Alarm Communicator (DACT) (Model 7100-D)
RS-232 Printer Transient Module (PTRM), Supervised
Municipal Circuit Option Module (MCOM)
1.3 Control and Indicators
1.3.1 Switch Controls
Alarm Acknowledge
Trouble Acknowledge
Signal Silence
System Reset/Lamp test
Programming buttons
- Menu/Back
- Back Space/Edit
- OK
12 button keypad
1.3.2 LED Indicators
AC Power On
(green)
Ground Fault
(yellow)
Alarm
(red)
NAC 1 Silenced
(yellow)
Supervisory
(yellow)
NAC 2 Silenced
(yellow)
System Trouble
(yellow)
System Silenced
(yellow)
Power Fault
(yellow)
1.3.3 Audible Sounder
An Alarm/Trouble sounder is located on the Basic System Module (BSM).
1.4 Optional Modules
The following optional modules and features are available:
1.4.1 Digital Alarm Communicator (DACT)
The Model 7100-D provides an integral digital communicator (DACT), fully
programmable from the keypad, which is compatible with Digital Alarm Receivers
(DACRs) that can receive the following formats:
SIA DC8
SIA DCS20
Ademco Contact ID
3+1 1400 Hz
3+1 2300 Hz
4+2 1400 Hz
4+2 2300 Hz
1.4.2 Class A Option Module (CAOM)
All 7100 Models are supplied with Class B Notification Appliance Circuits and
Class B Signaling Line Circuits. For Class A operation, the addition of a CAOM
Module is required. This module operates with all 7100 Models and enables the
signaling line circuits to operate as Class A, Style 6 or 7 and notification
appliance circuits to operate as Class A, Style Z. It supplies the additional
terminals for these circuits.
Fi
g
ure 2