Installation Manual

9000-0447 Rev. I
Page 4 of 42
1.0 System Overview
1.1 Description
The Gamewell-FCI 7100 is a multiprocessor-based analog/addressable system, de-
signed for commercial, industrial and institutional fire alarm applications. It is available
with either one or two signaling line circuits.
The 7100 Series is Listed by Underwriter’s Laboratories, Standard UL 864, 9th Edition. It
is suitable for the following signaling services:
Automatic Fire Detector Alarm
Manual Fire Alarm
Waterflow Alarm
Supervisory
Automatic Smoke Alarm, non-coded and master coded operation
Releasing Device Service
The 7100 Series complies with the requirements of the following National Fire Protection
Association (NFPA) Standards:
NFPA 13 - Installation of Sprinkler Systems
NFPA 16 - Deluge Foam-Water Sprinkler Systems
NFPA 72 - National Fire Alarm Code:
- Central Station Fire Alarm Systems
- Local Fire Alarm Systems
- Auxiliary Fire Alarm Systems
- Remote Station Fire Alarm Systems
- Proprietary Fire Alarm Systems
1.2 Features
1.2.1 Standard Features
Two (2) Class B, Style 4 Signaling Line Circuits
Two (2) Class B, Style Y Notification Appliance Circuits
Alarm and Trouble dry contacts
Accommodates 99 Gamewell-FCI Approved, UL Listed compatible analog
sensors per SLC
Accommodates 98 Gamewell-FCI Approved, UL Listed compatible
addressable monitor/control devices per SLC
80-character alphanumeric LCD display
280 event history buffer (non-volatile)
Power-limited
Resettable/Non-resettable 1.0 amp. @ 24 VDC power output, FWR
Alarm verification
Walk test
Multi-level alarm processing
Positive alarm Sequence (PAS) operation
NAC coding
Trouble reminder
Integral RS-232 port
Key Switch - keyed alike with the door lock and renders the key pad
inoperative until activated.