Installation Instructions
73
Galaxy 2 Series Installation Manual
52 - Zones
Option 52 - Zones
Zones are programmed in menu 52. Each zone has a set of attributes as shown in the following table:
Selecting Zones
On entering the option, the first zone on the system is displayed; the zone address, function and group as-
signed are displayed on the top line, the descriptor is displayed on the bottom line.
From the display of the first zone, any zone on the system can be displayed by pressing the A or B keys or by
entering the address of a specific zone.
The zone is selected for programming by pressing the ent key; the first zone programming attribute 1=Func-
tion is displayed.
Attributes
The attributes can be stepped through by pressing the A or B keys or directly selected by pressing the at-
tribute number (1–6). Once the required attribute is on display, press the ent key to gain access for modifica-
tion.
Once the attribute has been assigned press the ent key to save the programming and return to the attribute
selection level.
Attributes Description
1 Function Assigns Zone Type
2 Descriptor SMS text - 16 characters max. alpha-numeric description
3 Soak Test Zone monitored for 14 days max.
4 Omit enable When enabled zone can be by-passed by authorized user
5 RF options Zone set up with a wireless detector
6 Groups Assigns a zone to a single group on the system
Note: Groups only appear if the Groups option is enabled (refer to option 63.1)
Table 24. Zone Functions and Descriptions
Zone Function Description
0 Not Active For use in Part set. Zone is not active in alarms but tampers are monitored.
1Final
Activation whilst set initiates the timed entry procedure. Activation during setting may terminate setting
depending on programming.
2 Exit Intruder zone which is inactive during the setting and timed unsetting procedures.
3 Intruder Causes an instant intruder alarm when set.
4 24 Hours As an intruder zone but permanently active.
8 Push Set Terminates a setting procedure.
9 Keyswitch Transition to open initiates setting. Transition to closed causes unset. Simulates level 2 user.
13 PA Activates a PA alarm.
14 PA Silent Activates a silent PA alarm.
17 Link Has no alarm function but can be used to activate links.
18 Spare Renders all function of a particular zone inactive, including tampers, RF supervision and RF Low battery.
19 Fire Activates a fire alarm.
20 Tamper
Activates a tamper condition (both the physical alarm state and physical tamper state of the zone result in
the same tamper activation).
23 Batt Fail Causes an APS fault condition.
25 AC Fail Causes a PPS fault.
53 Secondary Entry
As Exit function but changes to entry upon the force omitting of a Final zone, as per the requirements of
DD243.
54 Assistance Activates an Assistance alarm.
55 Bell Fail Causes a bell fault condition
Table 23. Zone attributes