Installation Instructions

69
Galaxy 2 Series Installation Manual
2. EOL Resistor
This selects the resistor value for the end of line (EOL) resistor used in EOL double balance zone configura-
tions. Normally this should be 1000 ohms. The value entered is in hundreds of ohms, 01 = 100 ohms,
99 = 9900 ohms.
3. Contact Res
As for EOL Resistor but for Contact resistor.
47 = Set confirm
This parameter gives an external indication when the system has set. There are three options:
0. Off
1. Strobe (flashes for two seconds)
2. Strobe & Bell (indication for two seconds when set terminates)
50 = RF Options
This parameter has six options:
1. RF Fob Unset
This option assigns the operation of the keyfobs.
0 = Disable fobs
1 = Unset anytime (default)
2 = After Entry
2. Supervision
If no signal is received from each RF detector within this time window, a supervision alarm is generated.
0 = 2.0 hours (default)
1 = 3.6 hours
2 = 8.4 hours
3. Audible Jam
This parameter suppresses alert indications for audible jam faults and has two settings:
0 = No (always silent). This is the default.
1 = Yes (follows alert programming in parameter 23)
4. Audible Supervision
This parameter assigns the indication for supervision loss and has two options:
0 = No (always silent).This is the default
1 = Yes (follows alert programming in parameter 23)
5. Audible RF Low Bat
This parameter assigns the indication for RF low bat faults and has two options:
0 = No (always silent). This is the default.
1 = Yes (follows alert programming in parameter 23)
51 - Parameters (cont’d)