Installation Instructions
54
Galaxy 2 Series Installation Manual
Menu 30 - Test Options
Option 31 - Walk Test
Menu option 31 allows a selection of zones or a single zone to be put on walk test.
NOTE: Zones programmed with the following functions remain active during the walk test:
24 hours, PA, PA silent, Fire, Tamper, Batt Fail, AC Fail, Assistance, Bell Fail.
Menu Option 31 has two settings:
1 = Test All Zones
This option initiates a walk test that includes all zones that have the omit attribute enabled (refer to option 52 =
PROGRAM ZONES). When selected, the walk test starts immediately. The message NO ENTRIES is
displayed if all zones are non-omittable when selecting All Zones. Non-omittable zones are not included in this
test and remain active throughout the test.
2 = Selected Zones
This test option allows the user to select any zones, irrespective of function type, for walk testing. As many
zones as necessary may be added to the list before starting the test. Press the
77
77
7 key to include all groups in
the Walk Test. On entering this option the details of the first zone are displayed. Each zone required for test
can be selected using the A or B keys or by entering the zone number. Press the # to toggle the test status of
each zone in the Walk Test: the test status of the zone changes to TEST if it is included in the test and
# = TEST if it is not. When all the required zones have been selected, press the ent key to start the Walk
Test.
Once the Walk Test has started, opening a zone activates outputs programmed as Entry/Exit Horn. If a
single zone is open, the keypad displays the address and function of the zone. If multiple zones are open, then
the keypad indicates how many zones are open; the open zones can be viewed by pressing the A or B keys.
While the walk test is active the message WALK TEST ACTIVE / ESC to abort is displayed; press the #
key to view all zones that have been walk tested so far. To return to the Walk Test press the # key again.
NOTE: RF zones will also record the signal strength in reduced gain mode.
Ending the Walk Test
To terminate the walk test, press the esc key. The test will terminate automatically if no zones are activated for
20 minutes.
The results of the test can be viewed by accessing the event log (refer to option 22 = DISPLAY LOG).
Option 32 - Output Test
Menu option 32 allows each of the output function types to be scrolled through and toggled on/off by pressing
the ent key. If a user has activated the output test, they can only turn on the bells and strobe. No other output
types can be selected by the user. Refer to 53 = Outputs for a full description of each output function.
Test Options