Installation Manual

411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D 9
Product Description
CHAPTER 1 Product Description
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use
conventional input devices. The 411UDAC accepts waterflow devices, two-wire smoke detectors, four-wire smoke
detectors, pull stations and other normally-open contact devices. The unit also supervises AC voltage, telephone line
input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable Form-C relays and 12
VDC resettable special application power. The 411UDAC interfaces with the public switched telephone network and
is compatible with most central station receivers. A total of fifteen popular communications formats are supported,
including the industry standard Ademco Contact ID. The communicator also contains a unique DACT option that
eliminates 'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a 24 hour
period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the PK-411UD
Windows
®
95 based remote site programming software. The 411UDAC is supplied with a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched telephone network.
Any IBM compatible personal computer with Windows
®
3.1 or greater, with a 1200 baud Hayes
®
compatible modem
and Upload/Download software P/N PK-411UD, may serve as a service terminal.
1.1 Product Features
Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)
Programmable input channels
2-wire smoke (Inputs 1 & 3 only)
pull station
normally-open contact
host panel trouble (Slave Mode)
supervisory
supervisory autoresettable
waterflow (silenceable)
waterflow (nonsilenceable)
One Style Y (Class B) NAC (supplementary application)
Dual telephone lines
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
12 VDC operation
1.6 amps total system power
Alarm Verification
Signal Silence Inhibit
Autosilence
Trouble Reminder
Trouble Resound - troubles will resound the buzzer every 24
hours at midnight until the trouble is cleared
Optional DP-2 Dress Panel (required for Canadian
applications)